Can you put parallel feeders in the same conduit?
Similarly, it is asked, what is a parallel service?
Parallel conductors are often installed where large ampacity feeders or services are used. All of the paralleled conductors in each phase, neutral or grounded set must be the same length and be made from the same conductor material. They must be the same circular mil area and have the same type of insulation.
Also to know is, what is the minimum size feeder conductor for a parallel feeder?
Parallel conductor installations are covered in NEC 310.10(H) and are permitted for each phase, polarity, neutral, or grounded conductor in sizes 1/0 AWG and larger. Joining conductors in parallel is like having two or more smaller conductors connected at each end to make one larger conductor.