What is the voltage to ground of a 480v three phase three wire system?
Likewise, people ask, what is the voltage to ground in a 480v Delta?
The phase to ground voltage on a 480 volt ungrounded delta system is 480V. NEC 250.97 applies. The voltage to ground for ungrounded circuits is the greatest voltage between the given conductor and any other conductor of the circuit. For a 3-phase, 3-wire ungrounded 480-volt system the voltage to ground is 480-volts.
Thereof, what is the voltage to ground on a 480 volt Wye?
A typical three-phase service could be a 208/120-volt wye system, which would be 208 volts from any line conductor to either of the other two line conductors and 120 volts is measured from any of the line conductors to the neutral or grounded conductor. Another standard configuration is a 480/277-volt wye system.
For a 480 volt system if it is a wye system you will have a 277 volts to all three phases neutral. Any other voltages to grounded conductor is going to be a delta system, but they can vary some depending on where it is grounded, or if it is grounded at all.